• Language:
Online Support
PVC Compound-Type PVC/A
A.jpg

DESCRIPTION

  • Type PVC/A compound is used for insulation and sheathing for electric power cable.
TECHNICAL PROPERTIES
  • Application standards: IEC 60502, TCVN 5935, IEC 60811.
  • Maximum temperature condition in normal use is 700C.
  • Temperature setting (0C):140-145-150-155-160-165-170.
    .
  • Colors: Blue, Red, Yellow, Orange, Black, Grey, White or Green

Properties Test Method Test Condition Unit Value
Mechanical and physical properties 
 Without ageing       
Tensile Strength IEC 60811-1-1 - Mpa > 12,5
Elongation IEC 60811-1-1 - % > 150
After ageing        
Tesile strength
Variation, maximum 
IEC 60811-1-2 1000C, 168h MPa
%
> 12,5
± 25
Elongation
Variation, maximum
IEC 60811-1-2 1000C, 168h %
%
> 150
± 25
Heat shock test IEC 60811-3-1 1500C, 1h - no cracks
Electrical properties
Volume resistivity IEC 60502-1 200C Ω.cm > 1013
700C Ω.cm > 1010


PACKAGING
  • 25 kgs bag or depend on customer’s requirement